• Pure sine wave
• Output power factor 0.9
• Programmable power management outlets
• ECO (Efficiency Corrective Optimizer) operation for energy saving
• Very high efficiency in battery mode
• Boost and Buck AVR for voltage stabilization
• Multiple c
• Pure sine wave
• Output power factor 0.9
• Programmable power management outlets
• ECO (Efficiency Corrective Optimizer) operation for energy saving
• Very high efficiency in battery mode
• Boost and Buck AVR for voltage stabilization
• Multiple communications available
• 3-stage smart battery charging control
• Optional HID Power Device USB Port
MODEL | Otima II T 800 | Otima II T 1.1K | Otima II T 1.5K | Otima II T 2K | Otima II T 2.5K | Otima II 3K (L) | Otima II T 5K | |
CAPACITY | 800VA / 720W | 1100VA / 990W | 1500VA / 1350W | 2000VA / 1800W | 2500VA / 2250W | 3000VA / 2700W | 5000VA / 4500W | |
INPUT | ||||||||
Voltage | 110/115/120/127 VAC or 208/220/230/240 VAC | 208/220/230/240VAC | ||||||
Acceptable Voltage Range | 81-152 VAC or 162-290 VAC | 162-290 VAC | ||||||
Frequency Range | 60/50 Hz (Auto sensing) | |||||||
OUTPUT | ||||||||
Output Voltage | 110/115/120/127 VAC or 208/220/230/240 VAC | 208/220/230/240VAC | ||||||
Voltage Regulation (Batt. Mode) | ±1.5 % (Before battery alarm) | |||||||
Current Crest Ratio | 3:1 | |||||||
Harmonic Distortion | 2% max @ 100% linear load, 5% max @ 100% non-linear load (before low battery alarm) | |||||||
Frequency Range (Batt. Mode) | 50 Hz or 60 Hz ± 1 Hz | |||||||
Transfer Time | Typical 2-6 ms, 10ms max. | |||||||
Waveform (Batt. Mode) | Pure Sinewave | |||||||
EFFICIENCY | ||||||||
ECO Mode | 97% | |||||||
Buck & Boost Mode | 95% | |||||||
Battery Mode | ≧ 88%, up to 90% @ nominal battery voltage | ≧89%, up to 91% @ nominal battery voltage for 110/115/120/127 VAC ≧91%, up to 92% @ nominal battery voltage for 208/220/230/240 VAC | ≧91%, up to 92% @ nominal battery voltage | |||||
BATTERY | ||||||||
Type & Number | 12V/7 Ah x 2 | 12V/9Ah x 2 | 12V/7Ah x 4 | 12V/9Ah x 4 | 12V/7Ah x 6 | 12V/9Ah x 6 | 12V/10Ah x 6 | |
Charging Current (max.) | 1.5 A | |||||||
Charging Voltage | 27.4 VDC ± 1% | 54.8 VDC ± 1% | 82.1 VDC ± 1% | |||||
Typical Recharge Time | 4 hours recover to 90% capacity | |||||||
INDICATORS | ||||||||
LCD Display | AC Mode, Battery Mode, Load Level, Battery Level, Input Voltage, Output Voltage, Overload, Fault and Low Battery | |||||||
ALARM | ||||||||
Battery Mode | Sounding every 10 seconds | |||||||
Low Battery | Sounding every 2 seconds | |||||||
Overload | Sounding every second | |||||||
Fault | Continuously sounding | |||||||
PROTECTION | ||||||||
Full Protection | Overload, discharge, and overcharge protection | |||||||
PHYSICAL | ||||||||
Dimension,DxWxH(mm) | 397 x 145 x 220 | 455 x 145 x 220 | 421 x 190 x 318 | |||||
Net Weight (kgs) | 11.7 | 12.1 | 17.2 | 19.7 | 26.6 | 29 | 34.5 | |
ENVIRONMENT | ||||||||
Humidity | 0-90 % RH @ 0- 40°C (Non-condensing) | |||||||
Noise Level | Less than 45dB | |||||||
Altitude | 0~3000m, 10% de-rating for over 1000m | |||||||
MANAGEMENT | ||||||||
Smart RS-232/USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7/8/10, Linux and MAC | |||||||
Optional SNMP | Power management from SNMP manager and web browser |